APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2095 Issued:1959-05-01
Revised:2012-12-20
Style 2095 Multiple-conductor cable using non-integral jacket

Rating80 deg C, 300 Vac, Horizontal flame.
Conductor32 AWG minimum, solid or stranded.
Insulated ConductorLabeled or complying with manufacturer's AWM procedure.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductor is not specified. A barrier layer and/or fillers are optional. May use same or mixed AWG size.
CoveringOptional.
ShieldOptional.
JacketExtruded PVC.
Diameter of cable under jacket*Minimum average thicknessMinimum thickness at any point
0.350 inch or less15 mils12 mils
0.351 - 0.700 inch30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
*Major diameter if cable is flat or oval.
BraidOptional.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of electronic equipment and appliances. Tags may indicate the following: "600 volts Peak for Electronic use only".