Rating | 105 deg C, 600 Vac, FT2 flame, 60 deg C Wet, 60 deg C Oil. |
|
Insulation | Labeled or complying with manufacturer's AWM Conductors. |
|
Assembly | Two or more insulated conductors. Braid may be optionally applied over conductors and/or assemblies. Filler may be employed in the interstices to make the cable round. |
|
Shield | AL/Polyester tape shield with or without drain wire, in contact with the metal portion of the tape or polyester tape cabled around two or more 24 AWG - 16 AWG insulated conductors. |
|
Covering | Paper tape, 2 mils maximum thickness, may be employed under the overall jacket. |
|
Jacket | Extruded PVC or extruded TPE. |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.500 inch or less | 80 mils | 64 mils |
| 0.501 - 0.750 inch | 95 mils | 76 mils |
| 0.751-1.000 inch | 110 mils | 88 mils |
| 1.001-1.500 inch | 125 mils | 100 mils |
| 1.501-2.000 inch | 140 mils | 112 mils |
| 2.01-2.50 inch | 155 mils | 124 mils |
| 2.51-3.00 inch | 170 mils | 136 mils |
| 3.01 inch and larger | to be determined by investigation |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Special Use Outdoor power supply cord; 105 deg C dry, 60 deg C wet and 60 deg C oil where the acceptability of the combination is to be determined by Underwriters Laboratories Inc. |
|