APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20965 Issued:1997-07-02
Revised:2012-04-19
Style 20965 Multiple-conductor cable using non-integral jacket.

Rating105 deg C, 600 Vac, FT2 flame, 60 deg C Wet, 60 deg C Oil.
InsulationLabeled or complying with manufacturer's AWM Conductors.
AssemblyTwo or more insulated conductors. Braid may be optionally applied over conductors and/or assemblies. Filler may be employed in the interstices to make the cable round.
ShieldAL/Polyester tape shield with or without drain wire, in contact with the metal portion of the tape or polyester tape cabled around two or more 24 AWG - 16 AWG insulated conductors.
CoveringPaper tape, 2 mils maximum thickness, may be employed under the overall jacket.
JacketExtruded PVC or extruded TPE.
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.500 inch or less80 mils64 mils
0.501 - 0.750 inch95 mils76 mils
0.751-1.000 inch110 mils88 mils
1.001-1.500 inch125 mils100 mils
1.501-2.000 inch140 mils112 mils
2.01-2.50 inch155 mils124 mils
2.51-3.00 inch170 mils136 mils
3.01 inch and largerto be determined by investigation
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial Use Outdoor power supply cord; 105 deg C dry, 60 deg C wet and 60 deg C oil where the acceptability of the combination is to be determined by Underwriters Laboratories Inc.