APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 20966 Issued:1997-07-02
Revised:2019-11-07
Style 20966 Multiple Conductor Flat Cable with Extruded Non-integral Jacket.

Rating105 deg C, 600 Vac, Cable flame, Moisture Resistant 60 deg C. -40 C cold
Conductor8 AWG - 500 kcmil flat.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyCable consists of an overall jacket, two flattened 8 AWG to 500 KCMIL conductors and a member located in the center of the flattened conductors. The member consists of a polyester tape helically applied over the core with three insulated grounding conductors sizes in accordance with Table 6.3 of the Standard for Metal Clad Cables UL 1569, two or more 22-16 AWG insulated conductors, and two to five inner members consisting of an optional TPE or PVC jacket, an aluminum polyester tape with optional drain wire in contact with the metal portion of the tape or polyester tape cabled around two or more 24-16 AWG insulated conductors, and optional fiber optic conductor. Braid may be employed around conductors or assemblies.
ShieldOptional.
CoveringOptional.
JacketExtruded PVC or Extruded TPE
dia. in inches
0.500 or less80 mils min average64 mils minimum at any point
0.501-0.750 dia95 avg76 min
0.751-1.000 dia110 avg88 min
1.001-1.500 dia125 avg100 min
1.501-2.000 dia140 avg112 min
2.01-2.50 dia155 avg124 min
2.51-3.00 dia170 avg136 min
3.01 dia and largerto be determined by investigation
Misc.Fillers - Kevlar, Jute or Polypropylene fillers may be employed in the interstices of the member located in the center of the flattened conductors to make it round.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseSpecial use outdoor power supply cord.