Rating | 105 deg C, 600 Vac, Cable flame, Moisture Resistant 60 deg C. -40 C cold |
|
Conductor | 8 AWG - 500 kcmil flat. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Cable consists of an overall jacket, two flattened 8 AWG to 500 KCMIL conductors and a member located in the center of the flattened conductors. The member consists of a polyester tape helically applied over the core with three insulated grounding conductors sizes in accordance with Table 6.3 of the Standard for Metal Clad Cables UL 1569, two or more 22-16 AWG insulated conductors, and two to five inner members consisting of an optional TPE or PVC jacket, an aluminum polyester tape with optional drain wire in contact with the metal portion of the tape or polyester tape cabled around two or more 24-16 AWG insulated conductors, and optional fiber optic conductor. Braid may be employed around conductors or assemblies. |
|
Shield | Optional. |
|
Covering | Optional. |
|
Jacket | Extruded PVC or Extruded TPE |
| dia. in inches |
| 0.500 or less | 80 mils min average | 64 mils minimum at any point |
| 0.501-0.750 dia | 95 avg | 76 min |
| 0.751-1.000 dia | 110 avg | 88 min |
| 1.001-1.500 dia | 125 avg | 100 min |
| 1.501-2.000 dia | 140 avg | 112 min |
| 2.01-2.50 dia | 155 avg | 124 min |
| 2.51-3.00 dia | 170 avg | 136 min |
| 3.01 dia and larger | to be determined by investigation |
|
Misc. | Fillers - Kevlar, Jute or Polypropylene fillers may be employed in the interstices of the member located in the center of the flattened conductors to make it round. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Special use outdoor power supply cord. |
|