|
Rating | 60, 75, 80, 90 or 105 deg C, 300 Vac, FT-2 Flame, Cable Flame, Sunlight Resistant. |
|
Conductor | 18 AWG - 10 AWG, consists of seven or more strands. |
|
Insulation | Extruded PVC, 45 mils minimum average thickness, 40 mils minimum thickness at any point before separation, 27 mils minimum thickness at any point after separation. |
|
Assembly | Two or three conductors, similar to flexible cord Type SPT-2. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Low voltage outdoor application in lighting fixtures, or low voltage lighting cable. |
|