APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21011 Issued:1998-10-15
Revised:2019-11-07
Style 21011 Multiple-conductor cable using non-integral jacket

Rating150 deg C(insulation), 110 deg C(jacket), 600 Vac, Cable flame.
Conductor18 AWG - 10 AWG solid or stranded round, tinned or bare copper.
InsulationLabeled or complying with manufacturer's AWM procedure, 20 mils min average, 18 mils minimum at any point.
AssemblyConsists of two or three conductors, twisted together. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
JacketPVC
dia. in inches
0.425 or less45 mils min average36 mils minimum at any point
0.426-0.700 dia60 avg48 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection of Lighting Fixtures where the acceptability of the combination is to be determined by Underwriters Laboratories Inc.