APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21014 Issued:1999-01-21
Revised:2013-02-21
Style 21014 Multiple-conductor cable using non-integral jacket

Rating80 deg C, 300 Vac, Cable flame.
Conductor20 - 17 AWG solid or stranded.
InsulationExtruded PVC, 24 mils minimum average thickness, 22 mils minimum thickness at any point.
AssemblyTwo conductors.
JacketExtruded PVC, 24 mils minimum average thickness, 19 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring of Appliances and Electronic Equipment or External Interconnection of Electronic Equipment.