Rating | 60 or 80 deg C, 600 Vac, Cable Flame. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twistedsingles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable.Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of eachassembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Optional. A 6 mil or heavier PVC, PE, ETFE or XLPE covering may be extruded over the conductor assembly. |
|
Jacket | Extruded PVC |
| major diameter under jacket in inches | mils minimum average | mils minimum at any point |
| 0.700 or less | 30 | 24 |
| 0.701-1.000 | 45 | 36 |
| 1.001-1.500 | 60 | 48 |
| 1.501-2.500 | 80 | 64 |
| 2.501-4.00 | 110 | 88 |
| 4.001 and larger | 140 | 112 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection or Internal Wiring of electronic equipment. |
|