APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21036 Issued:1999-06-21
Revised:2012-07-19
Style 21036 Parallel Cable with Extruded Non-integral Jacket.

Rating60, 75, 80, 90, 105 deg C, 300 Vac, Cable flame.
Conductor18 AWG - 10 AWG stranded, flat.
InsulationLabeled or complying with manufacturer's AWM procedure
18-16 AWG conductor size45 mils min average40 mils minimum at any point
14 AWG65 avg58 min
12 AWG80 avg72 min
10 AWG95 avg85 min
AssemblyThree conductors, same as type SPT-3. Two circuit conductors and one grounding conductor. The grounding conductor shall be employing insulation 15 mils minimum average thickness and 13 mils minimum thickness at any point, color green or green/yellow and centrally located.
ShieldCopper 85% minimum coverage over the black and white conductor employing 36-34 AWG strands. Optional on grounding conductor. Alternatively, Aluminum Foil 100% coverage over the black and white conductor and 30% minimum coverage of a braided copper shield, 36-34 AWG, over the foil.
JacketExtruded PVC, 25 mils min average, 20 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring or external interconnection of electronic equipment where Type SPT-3 is required and the final acceptance of the component is dependent on its installation and use in or with complete equipment submitted to Underwriters Laboratories Inc.