Rating | 60, 75, 80, 90, 105 deg C, 300 Vac, Cable flame. |
|
Conductor | 18 AWG - 10 AWG stranded, flat. |
|
Insulation | Labeled or complying with manufacturer's AWM procedure |
| 18-16 AWG conductor size | 45 mils min average | 40 mils minimum at any point |
| 14 AWG | 65 avg | 58 min |
| 12 AWG | 80 avg | 72 min |
| 10 AWG | 95 avg | 85 min |
|
Assembly | Three conductors, same as type SPT-3. Two circuit conductors and one grounding conductor. The grounding conductor shall be employing insulation 15 mils minimum average thickness and 13 mils minimum thickness at any point, color green or green/yellow and centrally located. |
|
Shield | Copper 85% minimum coverage over the black and white conductor employing 36-34 AWG strands. Optional on grounding conductor. Alternatively, Aluminum Foil 100% coverage over the black and white conductor and 30% minimum coverage of a braided copper shield, 36-34 AWG, over the foil. |
|
Jacket | Extruded PVC, 25 mils min average, 20 mils minimum at any point. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection of electronic equipment where Type SPT-3 is required and the final acceptance of the component is dependent on its installation and use in or with complete equipment submitted to Underwriters Laboratories Inc. |
|