APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21053 Issued:1999-08-19
Revised:2012-04-18
Style 21053 Multiple-conductor cable using non-integral jacket.

Rating60, 75, 80, 90 or 105 deg C, 300 Vac, Cable flame.
Conductor18 AWG - 16 AWG, solid or stranded.
InsulationLabeled or complying with manufacturer's AWM procedure, 30 mils minimum average thickness, 27 mils minimum thickness at any point. Optional grounding conductor - Green or green/yellow employing insulation, 15 mils minimum average thickness, 13 mils minimum thickness at any point.
AssemblyTwo or three insulated conductors, the same AWG size, laid parallel to form a flat cable similar to Type SPT-2. Manufacturer shall maintain a complete description of each assemble. One grounding conductor is acceptable in addition to two circuit conductors but not in addition to three circuit conductors and shall be centrally located.
ShieldCopper braid over the black and white conductors, 85 percent minimum coverage on optional grounding conductor.
JacketExtruded PVC, 15 mils minimum average thickness, 12 mils minimum thickness at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or external wiring where Type SPT-2 is required and the acceptability of the combination is to be determined by Underwriters Laboratories.