Rating | 60, 75, 80, 90 or 105 deg C, 300 Vac, Cable flame. |
|
Conductor | 18 AWG - 16 AWG, solid or stranded. |
|
Insulation | Labeled or complying with manufacturer's AWM procedure, 30 mils minimum average thickness, 27 mils minimum thickness at any point.
Optional grounding conductor - Green or green/yellow employing insulation, 15 mils minimum average thickness, 13 mils minimum thickness at any point. |
|
Assembly | Two or three insulated conductors, the same AWG size, laid parallel to form a flat cable similar to Type SPT-2. Manufacturer shall maintain a complete description of each assemble. One grounding conductor is acceptable in addition to two circuit conductors but not in addition to three circuit conductors and shall be centrally located. |
|
Shield | Copper braid over the black and white conductors, 85 percent minimum coverage on optional grounding conductor. |
|
Jacket | Extruded PVC, 15 mils minimum average thickness, 12 mils minimum thickness at any point. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal or external wiring where Type SPT-2 is required and the acceptability of the combination is to be determined by Underwriters Laboratories. |
|