| Rating | 105 deg C, 600 Vac, Cable flame. |
|
| Insulation | Labeled or complying with manufacturer's AWM procedure, 10 mils min average, 9 mils minimum at any point. The designations of all styles of individual conductors used in making up the cable assembly shall be available. |
|
| Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together. The length of lay of the twisted conductors or groups is not specified. A barrier layer may be employed. |
|
| Shield | Optional. |
|
| Jacket | extruded PVDF |
| dia. in inches |
| 0.700 or less | 30 mils min average | 24 mils minimum at any point |
| 0.701-1.500 dia | 45 avg | 40 min |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | External wiring of appliances of electronic equipment. |
|