Rating | 60 deg C, 300 Vac, Horizontal flame. |
|
Conductor | 36 AWG - 6 AWG solid or stranded round, Copper, Copper Clad Steel, or Copper Alloy, Bare or Coated (Tin or Silver) |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. The designations of all styles of individual conductors used in making up the cable assembly shall be available. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors cabled together to form a round cable. A flat or oval cable may also be constructed with no more than three rows of single conductors or groups of conductors. the length of lay of the twisted conductors or groups is not specified. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or a thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing, and would be applied immediately over the twisted assembly or individual conductors or groups of conductors. |
|
Shield | Optional. |
|
Jacket | Extruded PVC |
| major dia. in inches |
| 0.700 or less | 30 mils min average | 24 mils minimum at any point |
| 0.701-1.000 dia | 45 avg | 36 min |
| 1.001-1.50 dia | 60 avg | 48 min |
| 1.501-2.500 dia | 80 avg | 64 min |
| 2.501-4.000 dia | 110 avg | 88 min |
| 4.001 dia and larger | 140 avg | 112 min |
| |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring |
|