APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21080 Issued:2000-01-24
Revised:2019-11-07
Style 21080 Multiconductor Cable with Extruded Non-integral Jacket.

Rating75 deg C, 300 Vac, Cable flame.
Conductor30 AWG - 4/0 AWG solid or stranded round, tinned or bare copper. May include mixed AWG sizes.
InsulationLabeled or complying with Manufacture's AWM Procedure.
AssemblyTwo or more insulated singles twisted together. Lay not specified. Fillers and/or barrier layers optional. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional. A 6 mil, or heavier, FRPE covering may be extruded over conductor assembly.
ShieldOptional.
JacketFRPE
dia. in inches
0.700 or less25 mils min average20 mils minimum at any point
0.701-1.00 dia45 avg36 min
1.001-1.500 dia60 avg48 min
1.501-2.500 dia80 avg64 min
2.501-4.000 dia110 avg88 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of appliances and external interconnection of electronic equipment.