Rating | 60 deg C, 150 Vac, Horizontal flame, Cable Flame. |
|
Conductor | 36 AWG - 9 AWG solid or stranded round, tinned or bare copper. |
|
Insulation | Labeled or complying with Manufacturer's AWM Procedure. |
|
Assembly | Two or more individually insulated conductors or groups of insulated conductors laid parallel or cabled together to form a flat, oval or round cable. Conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. The use of a barrier layer and/or fillers is optional. Cable may contain Labeled Flat Ribbon Style AWM which may be rolled or spiralled and formed around fillers or bunched singles. Fillers and/or tape wrap or extruded covering may be used. |
|
Shield | Optional. The shield may be over one or more of the insulated conductors or applied between the conductor assembly and the optional covering. |
|
Covering | Optional. A 5 mil or heavier PVC covering may be extruded over one or more groups of conductors. |
|
Jacket | Extruded FRPE |
| major dia. in inches |
| 0.700 or less | 30 mils min average | 24 mils minimum at any point |
| 1.001-1.50 dia | 60 avg | 48 min |
| 1.501-2.500 dia | 80 avg | 64 min |
| 2.501-4.000 dia | 110 avg | 88 min |
| 4.001 dia and larger | 140 avg | 112 min |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection or internal wiring of electronic equipment. |
|