APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21096 Issued:2000-05-25
Revised:2019-11-07
Style 21096 Multiple conductor cable using extruded non-integral jacket

Rating60 deg C, 600 Vac, Cable flame.
Conductor40 AWG - 4 AWG solid or stranded.
InsulationLabeled or complying with Manufacturer's AWM Procedure.
AssemblyConsists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldOptional.
CoveringOptional, a 6 mil or heavier extruded PVC covering may be extruded over the conductor assembly.
JacketExtruded PVC
dia. in inches
0.425 or less30 mils min average24 mils min at any point
0.426-0.700 dia6048
0.701-2.500 dia8064
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or external interconnection of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024