Rating | 80 deg C, 600 Vac, Horizontal or cable flame. |
|
Conductor | 50 AWG - 2000 kcmil solid or stranded round, tinned or bare copper. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. Two or more jacketed members may be bonded together forming a flat cable. |
|
Shield | Optional. |
|
Covering | Optional. A 10 mil or heavier THV covering may be extruded over the conductor assembly. |
|
Jacket | Extruded THV |
| use | major diameter in inches | mils min average thickness | mils min at any point |
| internal | 1.500 or less | 10 | 8 |
| external | 0.700 inches or less | 30 | 24 |
| | 0.701-1.000 | 45 | 36 |
| | 1.001-1.500 | 60 | 48 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection of electronic equipment. |
|