APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21114 Issued:2000-08-21
Revised:2019-11-07
Style 21114 Multiconductor Cable with Extruded Non-Integral Jacket.

Rating150 deg C, 600, 1000 Vac, cable flame, Oil Resistant 80 deg C (optional).
Conductor50 AWG - 2000 kcmil solid or stranded round. The designations of all styles of individual conductors used in making up the cable assembly shall be available.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. If more than one group is used, groups shall also be twisted together. The length of lay of the twisted conductors or groups is not specified. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or thermoplastic-tape wrap. Such a barrier would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
ShieldOptional.
CoveringOptional.
JacketExtruded FEP
dia. in inches
0.425 or less25 mils min average20 mils minimum at any point
0.426-0.700 dia30 avg24 min
0.701-1.500 dia45 avg36 min
1.501-2.500 dia60 avg48 min
2.501 dia and larger80 avg. 64 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection or internal wiring of appliances or electronic equipment. In addition, the tag may also indicate the following: Suitable for immersion in oil at 80 deg C, or 600 V peak - For Electronic Use Only

UL and the UL Logo are trademarks of UL LLC © 2024