Rating | 60 deg C, 30 Vac, Horizontal flame (construction B) Cable flame (construction A). |
|
Conductor | 40 AWG minimum. Solid or stranded. |
|
Insulation | Labeded or complying with Manufacture's AWM Procedure. |
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval, or round cable. The lay of the insulated conductors are not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Covering | Optional. A 6 mils or heavier PVC covering may be extruded over the conductor assembly. |
|
Shield | Required. |
|
Jacket | Extruded XLPE. |
| | Construction A | | Construction B |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point | Minimum average thickness | Minimum thickness at any point |
| 0.350 inch or less | 20 mils | 17 mils | 15 mils | 12 mils |
| 0.351-0.700 inch | 30 mils | 24 mils | 30 mils | 24 mils |
| 0.701-1.000 inch | 40 mils | 36 mils | 40 mils | 36 mils |
| 0.101-1.500 mils | 54 mils | 38 mils | 54 mils | 38 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Construction A: Internal wiring or external interconnection of electronic equipment in Class 2 circuits only.Construction B: Internal wiring of electronic equipment in Class 2 circuits only. |
|