APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21146 Issued:2001-05-23
Revised:2011-10-24
Style 21146 Multi-conductor cable using non-integral jacket.

Rating105 deg C, 300 Vac, Cable flame, Oil Resistant 60 or 80C (whichever is applicable), Gasoline Resistant.
Conductor22-10 AWG, solid or stranded.
InsulationExtruded FEP, 22 - 19 AWG 7.5 mils min average, 6.5 mils min at any point. 18 - 10 AWG 10 mils min avg, 9 mils min at any point.
AssemblyIndividually insulated conductors cabled together. The length of lay of the twisted conductors is not specified. 1420 Denier Kevlar filler may be used. A barrier layer, if employed, may be polyester or a thermoplastic-tape wrap.
JacketExtruded PVC
Diameter under jacket in inchMin average thickness milsMin average thickness mils
0-0.7003024
0.701-1.0004536
1.001-1.5006048
1.501-2.5008064
CoveringExtruded Nylon, 5.0 min at any point. Recognized Component (QMTT2) nylon jacket compounds rated gasoline resistant
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection of electronic equipment.