APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21161 Issued:2001-07-11
Revised:2018-03-07
Style 21161 Multiple-Conductor Cable Using Extruded Non-Integral Jacket

Rating80 deg C, Voltage not specified, Horizontal flame.
Conductor36 AWG min. solid or stranded round, tinned or bare.
InsulationLabeled or complying with manufacturer's AWM Procedure. The designations of all styles of individual conductors used in making up the cable assembly shall be available.
AssemblyTwo or more individually insulated conductors or groups of Assembly insulated conductors cabled together to form a round cable. A flat or oval cable may also be constructed with not more than three rows of single conductors or groups of conductors. The length of lay of the twisted conductors or groups is not specified. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; thermoplastic covering, or thermoplastic-tape wrap. The barrier layer may be applied over the twisted assembly of individual conductors, groups of conductors or individual conductors or over the shield, if provided.
ShieldOptional - Location not specified.
JacketExtruded TPU
Diameter of core assembly under jacket (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
0.700 or less3024
0.701-1.0004536
1.001-1.5006048
1.501-2.5008064
2.501-4.00011088
4.001 and larger140112
Major diameter if cable is flat or oval
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring.