Rating | 75, 80, 90 deg C, 600, 1000 Vac, Horizontal flame, Cable flame, Optional - 60 or 75 deg Oil. |
|
Conductor | 40 AWG - 2000 kcmil. |
|
Insulation | Labeled or complying with Manufacturer's AWM Procedure. |
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Optional. Extruded PVC, 6 mil minimum thickness. |
|
Jacket | Extruded PVC |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inches or less | 50 mils | 40 mils |
| 0.701-1.000 inches | 60 mils | 48 mils |
| 1.001-1.500 inches | 80 mils | 64 mils |
| 1.501-2.500 inches | 110 mils | 88 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection or internal wiring of electronic equipment. Or External or Internal Wiring of Appliances where exposed to oil at a temperature not exceeding 60 deg. C or 75 deg. C (whichever is applicable) |
|