APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21183 Issued:2001-12-11
Revised:2011-10-03
Style 21183 Multiconductor Cable with extruded Non-integral Jacket

Rating105 deg C, 600 Vac, Horizontal flame, Cable flame.
Conductor36 AWG min. Solid or Stranded.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more individually insulated conductors or groups of insulated conductors cabled together to form a round cable. A flat or oval cable may also be constructed with not more than three rows of single conductors or groups of conductors. The length of lay of the twisted conductors or groups is not specified. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethylene terephthalate; or thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups of conductors.
ShieldOptional.
JacketTPE
dia of the cable under jacket is 0-0.700 inches30 mils min average24 mils minimum at any point
0.701-1.000 in45 avg36 min
1.001-1.500 in60 avg48 min
1.501-2.500 in80 avg64 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024