APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21194 Issued:2002-01-29
Revised:2008-05-27
Style 21194 Jacketed Cable.

Rating125 deg C, 600 Vac, Cable flame.
Conductor50 AWG - 2000 kcmil solid or stranded round, tinned or bare copper.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. May use same or mixed AWG size.
ShieldOptional.
CoveringOptional.
JacketTPE - See Facing Page for Compound. major dia. in inches of 0.700 or less, 30 mils min average, 24 mils minimum at any point; 0.701-1.000 dia, 45 avg, 36 min; 1.001-1.500 dia, 60 avg, 48 min; 1.501-2.500 dia, 80 avg, 64 min; 2.501-4.000 dia, 110 avg, 88 min; 4.001 dia and larger, 140 avg, 112 min.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or external wiring.
 
UL and the UL Logo are trademarks of UL LLC © 2024