APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21213 Issued:2002-04-26
Revised:2011-10-14
Style 21213 Multiconductor Cable with Extruded Non-Integral Jacket.

Rating80 deg C, 30 Vac, Cable flame.
Conductor50 AWG min. solid or stranded round.
InsulationLabeled or complying with Manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
CoveringOptional. A 6 mil or heavier PVC covering may be extruded over the conductor assembly.
ShieldOptional.
JacketTPU/PVC Blend
Diameter of Cable under Jacket in inchMinimum Average thickness in milsMinimum thickness at any point in mils
0.700 or less3024
0.701-1.0006048
1.001-1.50180 avg64 min
; #- Major diameter if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnect or internal wiring of electronic equipment.