Rating | 80 deg C, 300 Vac, Cable flame. |
|
Insulated Conductor | Labeled or complying with Manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Optional. Extruded PVC, over the conductor assembly, 6 mils minimum thickness at any point. |
|
Jacket | Extruded PVC/TPU. |
| Dia. of cable under jacket@ | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 60 mils | 48 mils |
| 1.001-1.501 inch | 80 mils | 64 mils |
| @ - Major diameter if cable is flat or oval. |
|
Braid | Optional. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External wiring or internal wiring. |
|