APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21219 Issued:2002-09-17
Revised:2011-12-20
Style 21219 Multiconductor Cable with Extruded Non-Integral Jacket.

Rating60, 75, 90, 105 deg C, 300 Vac, Horizontal flame, Cable Flame.
ConductorStranded Copper, 18 AWG - 10 AWG, stranding same as for SPT-3 per UL 62.
InsulationExtruded PVC, the nominal insulation thickness away from tear areas is 32 mils; min. at any point before separation is 28 mils; min. at any point after separation is 13 mils.
AssemblyTwo circuit conductors and one grounding conductor, same as type SPT-3. Min. distance between conductors is 54 mils.
Shield34 - 36 AWG copper wire spiral serve, applied over the Insulated Conductor Assembly, min. 85 % coverage.
JacketExtruded PVC.
Wire Size (AWG)Minimum Average Thickness (mils)Minimum Thickness At any Point (mils)
18-163834
145852
127365
108879
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal Wiring.