Rating | 90 deg C, 600 Vac, Cable flame. |
|
Conductor | 40 AWG - 1000 kcmil solid or stranded round, tinned or bare copper. |
|
Insulation | TPE |
| 40-9 AWG conductor size | 30 mils min average | 27 mils minimum at any point |
| 8-7 AWG | 45 avg | 41 min |
| 6-2 AWG | 60 avg | 54 min |
| 1-4/0 AWG | 80 avg | 72 min |
| 250-500 kcmil | 95 avg | 86 min |
| 550-1000 kcmil | 110 avg | 99 min |
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors. The conductors or groups of conductors may be laid parallel to form a flat, oval or round cable construction. The lay of the conductors is not specified. Barrier layer and/or fillers optional. May use same or mixed AWG sizes. Manufacturer shall maintain a complete description of each assembly. |
|
Shield | Optional. |
|
Jacket | PVC |
| dia. in inches |
| 1.500 or less* | 80 mils min average | 64 mils minimum at any point |
| 1.501-2.500 dia | 110 avg | 88 min |
| 2.501-3.500 dia | 140 avg | 112 min |
| 3.501 dia and larger | 160 avg | 128 min |
| *For parallel constructions, use the measured minor core dimension under the jacket to determine the jacket thickness required. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring or external interconnection of electronic equipment. |
|