APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21236 Issued:2002-12-27
Revised:2013-01-30
Style 21236 Multiple-Conductor Cable Using Extruded Non-Integral Jacket

Rating90 deg C, 600 Vac, Cable flame.
Conductor36 AWG - 2 AWG solid or stranded round, tinned or bare.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs or groups of twisted singles twisted together or singles or groups of singles. Lay not specified. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
FillersOptional- In accordance with the standard.
TapesOptional- In accordance with the standard.
ShieldOptional.
CoveringOptional. A 6 mil minimum thickness or thicker PVC covering may be extruded over two or more conductors or the conductor assembly.
JacketExtruded TPU
Diameter of core assembly under jacket (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
0.700 or less4334
0.701-1.0005342
SEE FACING PAGE FOR COMPOUND
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal interconnection of electronic equipment.