APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21266 Issued:2003-05-13
Revised:2012-04-19
Style 21266 Multiple-conductor cable using non-integral jacket

Rating80 deg C, 600 Vac, Cable flame.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more individually insulated wires or group of individually insulated wires cabled together. Fillers may be used in a cable but are not required. A barrier layer, if employed, may be a fibrous wrap serving, or braid; paper; nylon; oriented polyethyelene terephthalate; or thermoplastic-tape wrap. Such a barrier layer would serve to protect the cable during further processing and would be applied immediately over the twisted assembly of individual conductors or groups or conductors. May be formed in a round or flat assembly.
ShieldOptional.
JacketExtruded FRPE.
Dia. of cable under jacket@Minimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.010-1.500 inch60 mils48 mils
1.501-2.500 inch80 mils64 mils
@ - Major diameter if cable is flat or oval
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or External Wiring.