| Rating | 80 deg C, 150 Vac, Cable flame. |
|
| Conductor | 40 AWG min., solid or stranded. |
|
| Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
| Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturers shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
| Covering | Optional. A 5 mil or heavier extruded FRPE or PVC covering over the conductor assembly. |
|
| Shield | Optional. Over one or more of the insulated conductors or between the conductor assembly and the optional covering. |
|
| Jacket | Extruded FRPE thickness (in mils). |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
|
| Standard | Appliance Wiring Material UL 758. |
|
| Marking | General. |
|
| Use | External interconnection. |
|