Rating | 80 deg C, 1000 Vac, Cable flame. |
|
Insulated Conductors | No. 40 AWG minimum. Labeled or complying with manufacturer's AWM Procedure having a minimum rating of 80 deg C, 1000 Volts.
|
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. The lay of the conductors is not specified. A barrier layer and/or fillers are optional. Manufacturers shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Covering | Optional. A 5 mil or heavier FRPE or PVC covering over the conductor assembly. |
|
Shield | Optional. Over one or more of the insulated conductors or between the conductor assembly and the optional covering. |
|
Jacket | FRPE |
| Dia. of round assembly under jacket in inches | Minimum average thickness (mils) | Minimum thickness at any point (mils) |
| 0.700 or less | 30 | 24 |
| 0.701 - 1.000 | 45 | 36 |
| 1.001 - 1.500 | 60 | 48 |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External interconnection. |
|