APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21320 Issued:2004-03-01
Revised:2019-11-07
Style 21320 Multiple-conductor cable using non-integral jacket

Rating80 deg C, 1000 Vac, Cable flame.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more singles, twisted pairs or groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval, or round cables. May use same or mixed AWG size. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly.
ShieldOptional.
CoveringOptional.
JacketPUR
dia. in inches
0.700 or less30 mils min average24 mils minimum at any point
0.701-1.000 dia45 avg36 min
1.001-1.500 dia60 avg48 min
1.501-2.500 dia80 avg64 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring and external interconnection of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024