APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21350 Issued:2004-04-27
Revised:2012-04-25
Style 21350 Multiple-conductor cable using non-integral jacket.

Rating60 deg C, 30 Vac, Cable flame.
Conductor30 AWG - 4/0 AWG solid or stranded round. May include mixed AWG sizes.
InsulationLabeled or complying with Manufacture's AWM Procedure.
AssemblyTwo or more insulated singles twisted together. Lay not specified. Fillers and/or barrier layers optional. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional. A 6 mil, or heavier, FRPE covering may be extruded over conductor assembly.
ShieldOptional.
JacketExtruded FRPE
Diameter of core assembly under jacketMinimum average thicknessMinimum thickness at any point
0.700 inch or less30 mils24 mils
0.701-1.000 inch45 mils36 mils
1.001-1.500 inch60 mils48 mils
1.501 inch and larger80 mils64 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of appliances and external interconnection of electronic equipment.