Rating | 80 deg C, 300 Vac, Cable flame, Sunlight Resistant. |
|
Conductor | 50 AWG - 2000 kcmil solid or stranded round, tinned or bare copper. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Covering | Optional. |
|
Braid | Optional. |
|
Jacket | PVC |
| major dia. in inches |
| 0.700 or less* | 30 mils min average | 24 mils minimum at any point |
| 0.701-1.000 dia | 45 avg | 36 min |
| 1.001-1.500 dia | 60 avg | 48 min |
| 1.501-2.500 dia | 80 avg | 64 min |
| 2.501-4.000 dia | 110 avg | 88 min |
| 4.001 dia and larger | 140 avg | 112 min |
| *Sunlight Resistant PVC Jackets will be subjected to 720 h Weatherometer Exposure (see Facing Page) or employ a Recognized Component Polymeric Materials for Use in Wire and Cable (QMTT2) PVC 720 h Sunlight Resistant jacket compound. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. "Sun Res" or "Sunlight Resistant". |
|
Use | Internal wiring or external interconnection and sunlight resistant |
|