Rating | 125 deg C, 300 Vac, Cable flame. |
|
Insulation | Labeled or complies with manufacturer's Procedure. |
|
Assembly | Two or more singles, twisted pairs or groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval, or round cables. May use same or mixed AWG size. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. |
|
Covering | Optional. |
|
Shield | Optional. |
|
Jacket | Extruded XLPE. |
| Dia. of cable under jacket@ | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
| @ - Equivalent diameter of flat assembly = 1.1284 x (TW)^0.5 where T is the thickness of the assembly under jacket, and W is the width of the assembly under jacket |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring and external wiring. |
|