Rating | 125 deg C, 600 Vac, Cable flame. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure with minimum rating of 125?C, 600 V. |
|
Assembly | Two or more singles, twisted pairs or groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval, or round cables. May use same or mixed AWG size. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. |
|
Shield | Optional. |
|
Covering | Optional. |
|
Jacket | XLPE |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring and external interconnection of electronic equipment. |
|