Rating | 90 deg C, 600 Vac, Cable flame. |
|
Insulation | Labeled or complying with manufacturer's AWM Procedure. |
|
Assembly | Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Overall Assembly - The PVC Jacket extends to form a Web 750 mils wide between conductors; Web Minimum Average thickness and the Minimum Thickness at any point is an extension of the Jacket Thickness. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size. |
|
Shield | Optional. |
|
Jacket | Extruded PVC |
| @ Diameter of Cable under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
| 2.501-4.000 inch | 110 mils | 88 mils |
| 4.001 or larger | 140 mils | 112 mils |
| @ Major dia if cable is flat or oval. |
|
Braid | Optional. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring and/or external interconnection. |
|