APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21453 Issued:2005-09-30
Revised:2019-11-07
Style 21453 Multiple-conductor cable using non-integral jacket.

Rating60 deg C, 30 Vac, Horizontal flame.
Insulated ConductorLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more insulated conductors.
CoveringOptional.
ShieldOptional.
JacketExtruded MPPE-PE
dia. in inches
0.250 or less15 mils min average12 mils minimum at any point
0.251-0.424 dia30 avg24 min
0.425-0.700 dia60 avg48 min
0.701-1.500 dia80 avg64 min
1.501-2.500 dia110 avg88 min
2.501 dia and larger140 avg112 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring in Class 2 circuits.

UL and the UL Logo are trademarks of UL LLC © 2024