Rating | 60 deg C, 30 Vac, Horizontal flame. |
|
Insulation | Labeled or complying with manufacturers procedure. |
|
Assembly | Two or more insulated conductors. |
|
Covering | Optional. |
|
Shield | Optional. |
|
Jacket | Extruded mPPE-PE |
| Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.250 inch or less | 15 mils | 12 mils |
| 0.251-0.424 inch | 30 mils | 24 mils |
| 0.425-0.700 inch | 60 mils | 48 mils |
| 0.701-1.500 inch | 80 mils | 64 mils |
| 1.501-2.500 inch | 110 mils | 88 mils |
| 2.501 inch and larger | 140 mils | 112 mils |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring in Class 2 circuits and both ends are terminated in connectors. |
|