Rating | 60 deg C, 30 Vac, Cable flame |
|
Conductor | 50 AWG - 2000 kcmil solid or stranded |
|
Insulation | Labeled or complies with Manufacturers AWM Procedure |
|
Assembly | Two or more insulated singles or groups of insulated singles cabled together to form a flat, oval or round assembly. Barrier layer and/or fillers optional. May use same or mixed AWG size. |
|
Shield | Optional |
|
Jacket | Extruded TPE |
| @Diameter of core assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0.700 inch or less | 30 mils | 24 mils |
| 0.701-1.000 inch | 45 mils | 36 mils |
| 1.001-1.500 inch | 60 mils | 48 mils |
| 1.501-2.500 inch | 80 mils | 64 mils |
| 2.501-4.000 inch | 110 mils | 88 mils |
| 4.001 inch and larger | 140 mils | 112 mils |
| |
| @ - Major diameter if cable is flat or oval |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General |
|
Use | Internal Wiring and External Interconnection |
|