APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21482 Issued:2006-02-20
Revised:2019-11-07
Style 21482 Multi-conductor cable using non-integral jacket

Rating80 deg C, 600 Vac, Horizontal flame.
Conductor36 AWG min. solid or stranded round.
InsulationLabeled or complying with manufacturers AWM Procedure.
AssemblyTwo or more insulated singles or groups of insulated singles cabled together to form a flat, oval or round assembly. Barrier layer and/or fillers optional. May use same or mixed AWG size. Manufacturer shall maintain a complete description of each assembly.
ShieldOptional.
CoveringOptional.
BraidOptional.
JacketExtruded TPE
major dia. in inches
0.700 or less45 mils min average36 mils minimum at any point
0.701-1.000 dia60 avg48 min
1.001-1.500 dia80 avg64 min
1.501-2.500 dia110 avg88 min
2.500 dia and larger140 avg112 min
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of electronic equipment.

UL and the UL Logo are trademarks of UL LLC © 2024