APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21550 Issued:2007-04-23
Revised:2011-10-20
Style 21550 Multiple-conductor cable using non-integral jacket.

Rating80 deg C, 30 Vac, Horizontal flame.
Insulated ConductorLabeled or complying with manufacturer's AWM procedure.
AssemblyTwo or more insulated conductors. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly.
CoveringOptional.
ShieldOptional.
JacketExtruded FRPE
Dia. of core assembly under jacketMin averageMinimum at any point
0.700 inches or less15 mils12 mils
0.701-1.500 dia30 mils24 mils
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring in Class 2 circuits only.