|
Rating | 90 deg C, 600 Vac, 60 deg C oil resistant, Cable flame. |
|
Insulated Singles | Labeled or complying with manufacturer's AWM Procedure with minimum rating of 90 C, 600 V. |
|
Assembly | Two or more insulated conductors. |
|
Covering | Optional. |
|
Shield | Optional. |
|
Jacket | XLPE. |
| Dia. of round assembly under jacket in inches | Minimum average thickness (mils) | Minimum thickness at any point (mils) |
| 0.7 or less | 30 | 24 |
| 0.701 - 1.000 | 45 | 36 |
| 1.001 - 1.500 | 60 | 48 |
| 1.501 - 2.500 | 80 | 64 |
| # Equivalent diameter of flat assembly = 1.1284 x (TW)0.5 where T is the thickness of the assembly under jacket, and W is the width of the assembly under jacket. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | Internal wiring and external wiring. |
|