APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21599 Issued:2008-08-20
Revised:2011-10-28
Style 21599 Multi-conductor cable using non-integral jacket

Rating150 deg C, 300 Vac, Cable flame.
Conductor30 AWG - 8 AWG, solid or stranded.
InsulationExtruded ETFE, 10 mils min average, 9 mils minimum at any point.
AssemblyTwo or more insulated conductors.Twisted singles or groups of twisted singles twisted together, or groups may be laid parallel to form flat, oval, or round cables. May use same or mixed AWG size. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly.
ShieldMetal braid.
JacketExtruded ETFE
Dia. under Jacket in inchMinimum average thickness milsMinimum thickness at any point mils
0.250 or less86
0.251 - 0.350108
0.351 - 0.5001310
0.501 - 0.7001512
0.701 - 1.5002016
Major diameter if cable is flat or oval.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal and external use.

UL and the UL Logo are trademarks of UL LLC © 2024