APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21660 Issued:2009-11-18
Revised:2012-04-24
Style 21660 Multiple conductor cable using non-integral jacket

Rating60 deg C, 30 Vac, Cable flame.
Conductor40 AWG - 10 AWG, solid or stranded.
InsulationFoamed PE, 6 mils minimum average, 5 mils minimum at any point.
AssemblyTwo or more insulated conductors. Filler and/or covering optional. Manufacturer shall maintain a complete description of each assembly. Diameter of assembly under jacket 2.500 inches maximum.
CoveringOptional.
ShieldOptional.
JacketPVC, 15 mils minimum average, 12 mils minimum at any point. For rippable construction, jacket thickness measurement made after ripping.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal wiring for use in or with Class 2 circuit.

UL and the UL Logo are trademarks of UL LLC © 2024