Rating | 105 deg C, 1000 Vac, Cable flame, Optional 60C Oil Resistant & Gasoline Resistant. |
|
Insulation | Labeled or complying with manufacturer's AWM procedure. |
|
Assembly | Consists of two or more conductors, twisted pairs or groups of twisted conductors twisted together. The conductors or groups of conductors may be laid parallel forming a flat, oval or round cable. A barrier layer and/or fillers are optional. Manufacturer shall maintain a complete description of each assembly. |
|
Shield | Optional. |
|
Covering | Optional inner layer. |
|
Jacket | PVC |
| Diameter of round assembly under jacket or equivalent diameter of flat assembly under jacket | Minimum average thickness | Minimum thickness at any point |
| 0 - 0.400 in | 30 mils | 24 mils |
| 0.401 - 0.700 in | 30 mils | 24 mils |
| 0.701 - 1.000 in | 45 mils | 36 mils |
| 1.001 - 1.500 in | 60 mils | 48 mils |
| 1.501 - 2.500 in | 80 mils | 64 mils | |
| - For flat assembly, calculated as 1.1284 x (TW)1/2 in which T is the thickness of the assembly under the jacket and W is the width of the assembly under the jacket. |
|
Standard | Appliance Wiring Material UL 758. |
|
Marking | General. |
|
Use | External Wiring |
|