APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21722 Issued:2010-09-30
Revised:2011-10-26
Style 21722 Multiple-conductor cable using non-integral jacket.

Rating90 deg C, 300 V, Cable flame.
Conductor50 AWG - 10 AWG, solid or stranded.
InsulationExtruded ETFE, 9 mils minimum average thickness, 8 mils minimum thickness at any point.
AssemblyTwo insulated conductors laid parallel or two or more insulated conductors or groups of insulated conductors cabled together. All conductors in any group twisted together. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
ShieldA metal tape and/or braid shall be provided under the jacket.
JacketExtruded TPU.; Dia of Cable under jacket, Minimum average thickness, Minimum thickness at any point; 0.700 inch or less, 30 mils, 24 mils; 0.701 - 1.000 inch, 45 mils, 36 mils; 1.001 - 1.500 inch, 60 mils, 48 mils; 1.501 - 2.500 inch, 80 mils, 64 mils.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseExternal wiring.

UL and the UL Logo are trademarks of UL LLC © 2024