APPLIANCE WIRING MATERIAL
Subj.758
Section
2
Page
21769
Issued:
2011-04-06
Revised:
2011-04-06
Style
21769
Jacketed Cable
Rating
105 deg C, -40 deg C(Optional), 1000 V, 60C or 80C Oil(Optional), Sun Res(Optional), Cable flame.
Conductor
50 AWG - 10 AWG, solid or stranded round
Insulation
Labeled.
Assembly
Two or more singles, twisted pairs of groups of twisted singles twisted together or singles or groups of singles may be laid parallel to form flat, oval or round cable. Lay not specified. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly. May use same or mixed AWG size.
Shield
Optional.
Covering
Optional inner layer.
Jacket
TPU - See Facing Page for Compound
Dia of Cable under jacket
Min average
Minimum at any point
0.700 inch or less
30 mils
24 mils
0.701-1.000 inch
45 mils
36 mils
1.001-1.500 inch
60 mils
48 mils
1.501-2.500 inch
80 mils
64 mils
Standard
Appliance Wiring Material UL 758.
Marking
General.
Use
External interconnect of appliances.
UL and the UL Logo are trademarks of UL LLC © 2024