APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21811 Issued:2012-01-26
Revised:New
Style 21811 Multiple-Conductor Cable with Extruded Jacket

Rating80 deg C, 30 Vac, Horizontal flame.
InsulationLabeled or complies with manufacturer's AWM Procedure
AssemblyTwo, three, or four parallel, or two or more twisted insulated singles or groups of twisted singles twisted together or groups of twisted singles may be laid parallel to form flat or oval cable. Barrier layer and/or fillers optional. Manufacturer shall maintain a complete description of each assembly.
ShieldOptional
JacketExtruded TPE, 16 mils minimum average thickness, 13 mils minimum thickness at any point
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal Wiring.

UL and the UL Logo are trademarks of UL LLC © 2024