APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 2185 Issued:1959-05-01
Revised:2012-04-06
Style 2185 Multiple-conductor cable using non-integral jacket.

Rating90 deg C, 600 Vac, Horizontal flame.
Conductor18 AWG - 2 AWG, stranded, tinned or bare copper.
InsulationExtruded PVC, 30 mils min average, 27 mils minimum at any point.
Assemblysame as type type ST.
JacketExtruded PVC, 60 mils min average, 48 mils minimum at any point.
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal wiring of air conditioning equipment.