APPLIANCE WIRING MATERIAL
Subj.758 Section 2 Page 21876 Issued:2012-10-11
Revised:2012-10-31
Style 21876 Multiple-Conductor Cable using Non-Integral Jacket

Rating90 deg C, 600 Vac, Cable flame.
Conductor30 AWG - 4/0 AWG, solid or stranded.
InsulationLabeled or complying with manufacturer's AWM Procedure.
AssemblyTwo or more insulated singles twisted together. Lay not specified. Fillers and/or barrier layers optional. Manufacturer shall maintain a complete description of each assembly.
Covering(Optional) Extruded thermoplastic covering may be extruded over conductor assembly, 6 mils minimum thickness at any point.
Shield(Optional) In accordance with the Standard.
JacketExtruded FRPE
Overall diameter (inches)Minimum average thickness (mils)Minimum thickness at any point (mils)
0.700 or less3024
0.701-1.0004536
1.001-1.5006048
1.501-2 .5008064
StandardAppliance Wiring Material UL 758.
MarkingGeneral.
UseInternal or External Wiring.